What to do if there is NX Unit Output Synchronization Error in Omron NX-AD?
- EedwardscurtisAug 25, 2025
If you encounter an NX Unit Output Synchronization Error in Omron I/O Systems, start by checking the CPU Unit for any errors and correct them. Then, inspect the communications cable connected to the Communications Coupler Unit for any damage or faulty connections, replacing or correctly wiring the cable as needed. If noise is affecting the communications cable, adjust the Consecutive Communications Error Detection Count parameter for the Communications Coupler Unit and implement noise countermeasures.
 