6 - 35
6 System Configuration and Setup
NX-series Safety Control Unit Users Manual (Z930)
6-9 Exporting/Importing Settings Data
6
6-9-3 Exporting/Importing Data for Individual Safety CPU Units
Precautions for Correct Use
When you import the data to the Safety CPU Unit, first configure all of the Safety I/O Units.
If importing data results in two or more Safety CPU Units, an error will occur. Delete the
Safety CPU Units that are not used.
You cannot import settings data that contains a Safety CPU Unit for which program data pro-
tection is set to Sysmac Studio version 1.16 or lower.
You cannot import settings data that contains a Safety CPU Unit for which user-defined func-
tion block data protection is set to Sysmac Studio version 1.11 or lower.