8 Checking Operation and Actual Operation
8 - 40
NX-series Safety Control Unit User’s Manual (Z930)
4 To check the temporary value, place the cursor over the value. The word Prepared is displayed
in the tooltip.
5 Select Force Values from the Controller Menu.
Forced refreshing is performed with the temporary values.
The light blue triangle at the lower left is removed, and the red triangle is displayed at the upper
left.
Example: The value of variable aaa is forced-refreshed to 100.
You can use forced refreshing for up to 19 variables at the same time.
Procedure to Cancel All Forced Refreshing from the FBD Editor
Use the following procedure to batch-clear forced refreshing.
Select Unforce Values from the Controller Menu.
All forced refreshing is cleared at once.
The red triangles at the upper left of all forced refreshing values are removed. The forced values will
remain unchanged.
A red triangle is displayed.