9 - 47
9 Troubleshooting
NX-series Safety Control Unit User’s Manual (Z930)
9-3 Checking for Errors with the Sysmac Studio
9
9-3-4 Error Descriptions
User Access Log
Event name Event Log Cleared Event code 9040 0000 hex
Meaning The event log was cleared.
Source Depends on where the Sysmac Stu-
dio is connected and the system con-
figuration.
Source details NX Unit Detection timing When com-
manded from
user
Error attributes Level Information Recovery --- Log category Access
Effects User program Continues. Operation Not affected.
System-defined
variables
Variable Data type Name
None None None
Cause and
correction
Assumed cause Correction Prevention
The event log was cleared by the
user.
--- ---
Attached
information
Attached information 1: Cleared events
1: The system event log was cleared.
2: The access event log was cleared.
Precautions/
Remarks
None
Event name Memory All Cleared Event code 90430000 hex
Meaning The Unit settings were cleared.
Source Depends on where the Sysmac Stu-
dio is connected and the system con-
figuration.
Source details NX Unit Detection timing When com-
manded from
user
Error attributes Level Information Recovery --- Log category Access
Effects User program Continues. Operation The Unit settings are cleared.
System-defined
variables
Variable Data type Name
None None None
Cause and
correction
Assumed cause Correction Prevention
The Clear All Memory operation was
performed.
--- ---
Attached
information
Attached information 1: Unit number of the NX Unit where the Clear All Memory operation was performed
Attached information 2: Execution results
0: Successful
1: Hardware error
2: Initialization failed
3: Initialization not possible
Precautions/
Remarks
Refer to the attached information for the results of the Clear All Memory operation.