6-9 Transistor (Open Collector)
System
Data
Constant No.
4th digit 3rd digit 2nd digit 1st digit
',
--- ---
' '
SPEED AGREED
SIGNAL IS SET
AT FACTORY
L
1
(R)
L
2
(S)
L
3
(T)
T
1
(U)
T
2
(V)
T
3
(W)
G(E)
IM
B1/
B2
POWER SUPPLY,
3-PHASE,
200/208/220 VAC
50 Hz
200/208/220/230 VAC,
60 Hz
MCCB
FORWARD
RUN/STOP
REVERSE
RUN/STOP
EXTERNAL
FAULT
INPUT
FAULT
RESET
MULTI-STEP
SPEED
SETTING 1
(MASTER/
AUX CHG.)
MULTI-STEP
SPEED
SETTING 2
INCHING
REFERENCE
EXTERNAL
COASTING
STOP
STANDARD
FUNCTIONS
SET AT
FACTORY
PRIOR TO
SHIPMENT
1
2
3
4
5
6
7
8
11
EXTERNAL
FREQ.
COMMAND
2kΩ
0TO+10V
4TO20mA
0TO10V
0V
P
P
12(G)
15
13
14
16
17
MULTI-FUNCTION
INPUT
FWD
REV
Eb
RESET
FORWARD BY
HOLDING INPUT
REVERSE BY
HOLDING INPUT
ANALOG
OUTPUT
FAULT CONTACT OUTPUT
CONTACT CAPACITY
LESS THAN 1 A FOR 250 VAC
AND 30 VDC
FREQ. METER (3 VDC, 1 mA)
21
22
(12)
18
19
20
9
10
25
27
MULTI-FUNCTION ANALOG
OUTPUT
STANDARD OUTPUT
FREQUENCY SETTING
OTO+10V
MULTI-FUNCTION OUTPUT
CONTACT CAPACITY LESS
THAN 1 A FOR 250 VAC
AND 30 VDC
SEQUENCE
COMMON
TERMINAL (0 V)
SHIELDED SHEATH
CONNECTION TERMINAL
POWER SUPPLY FOR
SPEED SETTING
+15 V, 20 mA
MASTER COMMAND
0TO10V(20kΩ)
MASTER COMMAND
4 TO 20 mA (250 Ω)
MULTI-FUNCTION
ANALOG INPUT
0TO10V(20kΩ)
26
MULTI-FUNCTION
OUTPUT OPEN
COLLECTOR 2
MULTI-FUNCTION
OUTPUT OPEN
COLLECTOR 1
”0 SPEED SIGNAL”
IS SET AT FACTORY
MOTOR
SYSDRIVE 3G3IV
0V
FM
FREQ. METER CALIBRATION
RESISTOR: RV30YN 20SB 20 kΩ
--+
SIGNAL DURING RUNNING
IS SET AT FACTORY
PRIOR TO SHIPMENT
2kΩ
P
VOLTAGE
SELECTION
M
COOLING
FAN
r
s
Transistor Operation
ON (Current sink state)
at closed contact
460/440/
415/400/380 V
L
1
(R)
L
2
(S)
L
3
(T)
Note
1. See notes on page 38.
2. Use the transistor open collector with withstand voltage 35 VDC and
above, rated current 100 mA and above.
Section 6-9