*Frequency reference setting
0: Set by frequency setting resistor
1: Digital operator set value (An-01)
"+
6-11 Run/Stop by Main Circuit Magnetic Contactor for Models
3G3IV-B2300
System
Data
Constant No.
4th digit 3rd digit 2nd digit 1st digit
',
---
# ' #
*
##
---
#
--- ---
For 230 V class, 40 Hp, 300 kW.
Turn on the power supply after checking that the motor has stopped. This
circuit cannot be used for an application with frequent run-stop (repeating
frequency: within 1 hour).
OFF ON
L
1
(R)
L
2
(S)
L
3
(T)
T
1
(U)
T
2
(V)
T
3
(W)
G(E)
IM
MCCB
1
2
3
4
5
6
7
8
11
12(G)
15
13
14
16
17
ANALOG
MONITOR
FREQ. METER (METER SPECIFI-
CATIONS 3 VDC, 1 mA)
21
22
(12) (32)
9
10
25
27
MULTI-FUNCTION ANA-
LOG OUTPUT 0 TO +10 V
STANDARD SETTING
OUTPUT FREQUENCY
MULTI-FUNCTION CONTACT OUTPUT
250 VAC, 1 A OR LESS.
30 VDC, 1 A OR LESS
26
MOTOR
0V
FM
FREQ. METER CALIBRATION
RESISTOR: RV30YN 20SB 20 kW
--
+
L
1
(R)
L
2
(S)
L
3
(T)
13
(P1) (P3) (N)
VS OPERATOR JVOP-95
OPEN COLLECTOR1
STANDARD SETTING
ZERO SPEED SIGNAL
OPEN COLLECTOR2
STANDARD SETTING
SPEED AGREED SIGNAL
MULTI-FUNCTION OUTPUT
COMMON
18
19
20
FAULT CONTACT OUTPUT
TRX
FAULT
CONTACT
SA
MC
TRX
MC
SA
a
b
a
b
a
b
MC
THREE-PHASE
POWER SUPPLY
200/208/220 VAC,
50 Hz
200/208/220/230 VAC,
50 Hz
L
1
(R)
MC
L
2
(S)
L
3
(T)
MCX
T
1
(U)
T
2
(V)
T
3
(W)
M
t1(r)
t2(S
)
SYSDRIVE 3G3IV
COOLING FAN
RUN COMMAND
STOP COMMAND
EXTERNAL FAULT INPUT
FAULT RESET
MULTI-FUNCTION
CONTACT INPUT
FWD/REV RUN
SELECT IS SET
TO TERMINAL
(5) FUNCTION
SEQUENCE COMMON
0VTERMINAL
SHIELD SHEATH
CONNECTION TERMINAL
POWER SUPPLY FOR SPEED
SETTING(+15 V, 20 mA)
MASTER REFERENCE
0TO10V(20K
Ω)
MASTER REFERENCE
4TO20mA(250
Ω)
MULTI-FUNCTION
ANALOG OUTPUT0
TO +10 V
GROUND
(100
Ω
OR LESS)
MCX
SA
SA: SURGE SUPPRESSOR
(DCR250A 33E C0024 71)
MCX: AUX RELAY (MY-2
OR EQUIVALENT)
STANDARD SETTING
DURING RUNNING
SIGNAL
MULTI-FUNC-
TION OUTPUT
Note
1. See notes on page 38.
2. Braking is not activated at deceleration stop. It coasts to a stop.
3. Use MC or MCX of delay release type for restart operation after momen-
tary power loss.
4. Frequency setting resistor is not required for the use of digital operator’s
set value as frequency reference.