48
2-8-6 Accel/Decel Time and Patterns
Item name Constant to be set Factory preset
Acceleration time 1 No. 9 10.0 s
Deceleration time 1 No. 10 10.0 s
Acceleration time 2 No. 11 10.0 s
Deceleration time 2 No. 12 10.0 s
Accel/Decel Time Select No. 32 or No. 33 No. 32 = 1, No. 33 = 3
Each item can be set from 0.0 sec to 600.0 sec.
The set time indicates the interval required before the maximum
output frequency No. 2 is reached.
Time marked with can be set for two-step switching using an
external contact.
The accel/decel time select command is input from multifunction
contact input terminals 4 and 5. Set the value of constant No. 32 to
6 to specify accel/decel time select operation for terminal 4, and
set the value of constant No. 33 to 6 to specify accel/decel time
select operation for terminal 5.
No. 2
No. 9
No. 12No. 11
Output frequency
No. 10

Between control circuit terminals 4 or 5 and 6.
Open: No. 9 and 10 are selected.
Closed: No. 11 and 12 are selected.
Time
Output frequency
2-8-7 Output Frequency Control (Gain/Bias)
Item name Constant to be set Factory preset
Frequency command gain No. 22 1.0
Frequency command bias No. 23 0.00
Output frequency (gain/bias) can be set freely according to fre-
quency setting (0 to 10 V or 4 to 20 mA)
No. 22
0
100%
No. 23
10 V
(4 mA) (20 mA)
Bias
(100% = 1.00)
Frequency setting
Gain
Description of Functions and Constants Section 2-8