57
2-8-18 Carrier Frequency
Item name Constant to be set Factory preset
Carrier frequency upper limit No. 40 4
Changing the carrier frequency reduces RFI noise and leakage
current without increasing motor noise.
Carrier frequency (kHz) = 2.5 kHz × constant No. 40 value
6
1
0
No. 40
Carrier frequency
: Factory setting prior to shipment
Output frequency
123456
Carrier frequency
(LOW) (HIGH)
Metallic noise
from motor
(Rather high) (Not audible)
4
Note Reduce continuous output current for changing the frequency to 5
or 6.
Carrier Frequency
Set Value
Maximum Continuous Output Current
1 to 4 Up to 100% of Inverter output current
5 Up to 90% of Inverter output current
6 Up to 80% of Inverter output current
If the wiring distance between the Inverter and motor is long,
reduce the carrier frequency. For details, refer to the wiring precau-
tions described in
1-4 Wiring
.
2-8-19 Speed Agreed Signal Output
Item name Constant to be set Factory preset
Frequency detection level No. 36 0.0 Hz
Multifunction contact output function No. 34 and No. 35 No. 34 = 0, No. 35 = 1
This function is used when operation at an arbitrary speed must be
indicated. Set the multifunction contact output (No. 34, No. 35) as
follows:
Set Value = 1: Frequency Agreed
Detection width
2 Hz
Output frequency
Frequency agreed signal
Release width
4 Hz
Frequency
reference
Closed
Description of Functions and Constants Section 2-8