3-37
3-7 Parameter List
3
Operation
Others
b078
Integrated power
clear
Cleared with the Enter key after changing to
01
00 Yes Yes
4-4
b079
Integrated power
display gain
1. to 1000. 1. Yes Yes
b082 Starting frequency 0.10 to 9.99 0.50 No Yes Hz 4-65
b083 Carrier frequency
0.5 to 15.0 (0.4 to 55 kW)
*Derating enabled
5.0 No No kHz
4-65
4-117
0.5 to 10.0 (75 to 132 kW)
*Derating enabled
3.0 No No kHz
b084 Initialization selection
00: Clears the trip monitor
01: Initializes data
02: Clears the trip monitor and initializes
data
00 No No
4-66
b085
Initialization
parameter selection
00
*Do not change.
00 No No
b086
Frequency
conversion
coefficient
0.1 to 99.0 1.0 Yes Yes 4-2
b087 STOP key selection
00: Enabled
01: Disabled
02: Disabled only during stop
00 No Yes 4-68
b088
Free-run stop
selection
00: 0 Hz start
01: Frequency matching start
02: Frequency pull-in restart
00 No Yes 4-69
b089
Automatic carrier
reduction
00: Disabled
01: Enabled
00 No No 4-71
b090
Usage rate of
regenerative braking
function
0.0 to 100.0 0.0 No Yes % 4-72
b091 Stop selection
00: Deceleration → Stop
01: Free-run stop
00 No Yes 4-68
b092 Cooling fan control
00: Always ON
01: ON during RUN
01 No Yes
4-72
b095
Regenerative
braking function
operation selection
00: Disabled
01: Enabled (Disabled during stop)
02: Enabled (Enabled during stop)
00 No Yes
b096
Regenerative
braking function ON
level
330 to 380
660 to 760
360/
72
0
No Yes V
b098 Thermistor selection
00: Disabled
01: PTC enabled
02: NTC enabled
00 No Yes
4-73
b099 Thermistor error level 0. to 9999.
3000.
No Yes Ω
Parameter
No.
Function name Monitor or data range
Default
setting
Changes during
operation
Unit Page
Normal
b031 = 10
* 2nd/3rd control is displayed when "SET(08)/SET3(17)" is allocated to one of multi-function inputs from C001
to C008.