6-7
6 I/O Allocation
CP2E CPU Unit Software User’s Manual(W614)
6-1 Allocation of Input Bits and Output Bits
6
6-1-4 Allocations to Expansion Units and Expansion I/O Units
z I/O Word Allocations to Expansion Units
Allocation Example: CPU Unit with 40 I/O Points + Temperature Senser Unit
(TS002) + Analog Output Unit (DA041) + Expansion I/O Unit with 40 I/O points
TS002
DA041
None
None
CPU Unit with 40 I/O Points
Input bits
Output bits
CIO 0.00 to CIO 0.11
CIO 1.00 to CIO 1.11
24 inputs
16 outputs
CIO 100.00 to CIO 100.07
CIO 101.00 to CIO 101.07
1st Unit:
CP1W-TS002
Temperature Sensor Unit
CIO 2 to CIO 5
2nd Unit:
CP1W-DA041
Analog Output Unit
3rd Unit:
Expansion I/O Unit with 40
I/O Points
CIO 102 to CIO 105
CIO 6.00 to CIO 6.11
CIO 7.00 to CIO 7.11
CIO 106.00 to CIO 106.07
CIO 107.00 to CIO 107.07
24 inputs
16 outputs
bit
Input bits
Output bits
15 14 13 1112 09 08 07 06 05
04
02 01 000310
CIO 0
CIO 1
CIO 2
CIO 3
CIO 4
CIO 5
CIO 6
CIO 7
CIO 100
CIO 101
CIO 102
CIO 103
CIO 104
CIO 105
CIO 106
CIO 107
CPU Unit with 40 I/O Points
CPU Unit with 40 I/O Points
Temperature Sensor Unit
Expansion I/O Unit with 40 I/O Points
Expansion I/O Unit with 40 I/O Points
Analog Output Unit
Cannot be used
Cannot be used
Cannot be used
Cannot be used