11-5
11 High-speed Counters
CP2E CPU Unit Software User’s Manual(W614)
11-1 Overview
11
11-1-2 Flow of Operation
Note 1 Only supported by N20/30/40/60 CPU Units.
2 Only supported by N30/40/60 CPU Units.
3 The same pulse input must be used for high-speed counter 0 and high-speed counter 1.
4 High-speed counter 2 cannot be used if the input setting of high-speed counter 0 or high-speed counter 1
is set for differential phase inputs (4x), pulse + direction inputs, or up/down pulse inputs.
5 CIO 0.07 to CIO 0.11 and CIO 1.00 to CIO 1.01 do not overlap with the high-speed counter function, so
they can also be used for high-speed counter.
E14 or N14 CPU Units
Note 1 The same pulse input must be used for high-speed counter 0 and high-speed counter 1.
2 High-speed counter 2 cannot be used if the input setting of high-speed counter 0 or high-speed counter 1
is set for differential phase inputs (4x), pulse + direction inputs, or up/down pulse inputs.
3 CIO 0.07 does not overlap with the high-speed counter function, so it can also be used for high-speed
counter.
CIO 0 09
−−−Normal input 9 Interrupt input 9
(Note 1)
Quick-response
input 9 (Note 1)
Pulse 3, Origin
input signal
(Note 2)
10
−−−Normal input 10 −−Pulse 0, Origin
proximity input
signal
11
−−−Normal input 11 −−Pulse 1, Origin
proximity input
signal
CIO 1 00
−−−Normal input 12 −−Pulse 2, Origin
proximity input
signal (Note 2)
01
−−−Normal input 13 −−Pulse 3, Origin
proximity input
signal (Note 2)
Input terminal block Pulse input method (Counting mode) Other functions that cannot be used at the same time
Terminal
block
label
Terminal
Increment
pulse input
Differential phase
×4 or up/down
input
Pulse/
direction
input
Normal input
Interrupt
input
Quick-
response
input
Origin
searches for
pulse outputs 0
and 1
CIO 0 00
High-speed
Counter 0,
increment
input
High-speed
Counter 0, phase A
or up input
High-speed
Counter 0,
pulse input
Normal input 0 −−−
01
High-speed
Counter 1,
increment
input
High-speed
Counter 0, phase B
or down input
High-speed
Counter 1,
pulse input
Normal input 1 −−−
02
High-speed
Counter 2,
increment
input
High-speed
Counter 1, phase A
or up input
High-speed
Counter 0,
direction
Normal input 2 Interrupt input 2 Quick-response
input 2
−
03
− High-speed
Counter 1, phase B
or down input
High-speed
Counter 1,
direction
Normal input 3 Interrupt input 3 Quick-response
input 3
Pulse 0, Origin
proximity input
signal
04
High-speed
Counter 3,
increment
input
High-speed
Counter 0, phase Z
or reset input
High-speed
Counter 0,
reset input
Normal input 4 Interrupt input 4 Quick-response
input 4
−
05
High-speed
Counter 4,
increment
input
High-speed
Counter 1, phase Z
or reset input
High-speed
Counter 1,
reset input
Normal input 5 Interrupt input 5 Quick-response
input 5
Pulse 1, Origin
proximity input
signal
06
High-speed
Counter 5,
increment
input
−−Normal input 6 Interrupt input 6 Quick-response
input 6
Pulse 0, Origin
input signal
07
−−−Normal input 7 Interrupt input 7 Quick-response
in
put
7
Pulse 1, Origin
input signal
Input terminal block Pulse input method (Counting mode) Other functions that cannot be used at the same time
Terminal
block
label
Terminal
Increment
pulse input
Differential phase
×4 or up/down
input
Pulse/
direction
input
Normal input
Interrupt
input
Quick-response
input
Origin searches
for pulse out-
puts 0 to 3

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron SYSMAC CP2E-E D Series and is the answer not in the manual?

Omron SYSMAC CP2E-E D Series Specifications

General IconGeneral
BrandOmron
ModelSYSMAC CP2E-E D Series
CategoryComputer Hardware
LanguageEnglish

Related product manuals