15 Ethernet
15-48
CP2E CPU Unit Software User’s Manual(W614)
TCP Socket Passive Open Request
Note These response codes will be returned only on large, multilevel networks.
TCP Socket Active Open Request
Note These response codes will be returned only on large, multilevel networks.
Response
code
Meaning
0000 Normal end
0105 Local IP address setting error.
1100 TCP socket number is not 1 to 8 or local TCP port number is 0.
110C Request Switch turned ON during other processing.
220F
Specified socket is already open or already processing an openrequest.
2211 Unit is busy; cannot execute.
2606 Specified socket is already open as UDP socket; cannot open TCP socket.
2607 Specified Socket Service Parameter Area is already being used foranother socket.
0045 Error in communications with remote node (ECONNABORTED).
0049 The same TCP port number has been specified more than once(EADDRINUSE).
004B (See note.) Error in communications with remote node (ECONNRESET).
0053 Error in communications with remote node (ETIMEDOUT) or remotenode does not exist.
0080 Open request timed out.
0081 The specified socket was closed during open processing.
Response
code
Meaning
0000 Normal end
0105 Local IP address setting error.
1100 TCP socket number is not 1 to 8 or local TCP port number is 0.
110C Request Switch turned ON during other processing.
220F Specified socket is already open or already processing an openrequest.
2211 Unit is busy; cannot execute.
2606 Specified socket is already open as UDP socket; cannot open TCP socket.
2607 Specified Socket Service Parameter Area is already being used foranother socket.
000D Remote IP address parameter error (EACCES).
0045 Error in communications with remote node (ECONNABORTED).
0049 The same port number has been specified more than once (EAD-DRINUSE).
004B (See note.) Error in communications with remote node (ECONNRESET).
004C Remote IP address parameter error (EADDRNOTAVAIL).Wrong parameter designation.An
attempt was made to set the local TCP port of the local node toActive Open.
0053 Communications error with remote node (ETIMEDOUT).No remote node.
0081 The specified socket was closed during open processing.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron SYSMAC CP2E-E D Series and is the answer not in the manual?

Omron SYSMAC CP2E-E D Series Specifications

General IconGeneral
BrandOmron
ModelSYSMAC CP2E-E D Series
CategoryComputer Hardware
LanguageEnglish

Related product manuals