A-93
Appendices
CP2E CPU Unit Software User’s Manual(W614)
A-2 Auxiliary Area Allocations by Address
App
A-2-2 Read/Write Words
A617 00 Serial Port 1/
Built-in RS232C Port
Communication Set-
tings
Display the present communication
settings of the serial port 1 or built-in
RS232C port. Reflect the PLC Setup
when power is turned ON.
Parity
0: Even
1: Odd
Retained See
Function
column.
Refreshed
when power is
turned ON.
01 Parity
0: Yes
1: No
Retained See
Function
column.
Refreshed
when power is
turned ON.
02 Stop bit
0: 2 bits
1: 1 bit
Retained See
Function
column.
Refreshed
when power is
turned ON.
03 Data length
0: 7 bits
1: 8 bits
Retained See
Function
column.
Refreshed
when power is
turned ON.
04 Start bit
0: 1 bit (fixed)
Retained See
Function
column.
Refreshed
when power is
turned ON.
08
to
11
Communication
speed
0 hex: Default (9600)
3 hex: 1200
4 hex: 2400
5 hex: 4800
6 hex: 9600
7 hex: 19200
8 hex: 38400
9 hex: 57600
A hex: 115200
Retained See
Function
column.
Refreshed
when power is
turned ON.
12
to
15
Communication
mode
0 hex: Default (Host
Link)
2 hex: NT link (1: N)
3 hex: Non-protocol
5 hex: Host Link
7 hex: Serial PLC
Link (Slave)
8 hex: Serial PLC
Link (Master)
9 hex: Modbus-RTU
Easy Master
D hex: Modbus-RTU
Slave
Retained See
Function
column.
Refreshed
when power is
turned ON.
A618 00 Serial Port 2/
Built-in RS-485 Port
Communication Set-
tings
Display the present communication
settings of the serial port 2 or built-in
RS-485 port. Reflect the PLC Setup
when power is turned ON.
Parity
0: Even
1: Odd
Retained See
Function
column.
Refreshed
when power is
turned ON.
01 Parity
0: Yes
1: No
Retained See
Function
column.
Refreshed
when power is
turned ON.
02 Stop bit
0: 2 bits
1: 1 bit
Retained See
Function
column.
Refreshed
when power is
turned ON.
03 Data length
0: 7 bits
1: 8 bits
Retained See
Function
column.
Refreshed
when power is
turned ON.
04 Start bit
0: 1 bit (fixed)
Retained See
Function
column.
Refreshed
when power is
turned ON.
Address
Name Function Settings
Status
after
mode
change
Status at
startup
Write
timing
Related
flags,
settings
Words Bits

Table of Contents

Related product manuals