Oracle Database Appliance Specifications
50 Oracle Database Appliance Owner's Guide • March 2017
Electrical Specifications
This section describes the electrical specifications for the various versions of Oracle Database
Appliance.
Electrical Specifications for Oracle Database Appliance X6-2
Series
Item Oracle Database
Appliance X6-2S
Oracle Database
Appliance X6-2M
Oracle Database
Appliance X6-2L
Oracle Database
Appliance X6-2-HA
Server
node
power
supply
output
rated
maximum
600W at 100-127 VAC
600W at 200-240 VAC
600W at 100-127 VAC
600W at 200-240 VAC
1000W at 100-127
VAC
1000W at 200-240
VAC
600W at 100-127 VAC
600W at 200-240 VAC
Server
node AC
power
7.2A at 100-127 VAC
3.4A at 200-240 VAC
7.2A at 100-127 VAC
3.4A at 200-240 VAC
8.5 -12A at 100-127
VAC
5.7A at 200-240 VAC
7.2A at 100-127 VAC
3.4A at 200-240 VAC
Storage
shelf
power
supply
output
rated
maximum
Not included Not included Not included 580W at 100-127 VAC
580W at 200-240 VAC
Storage
shelf AC
Power
Not included Not included Not included 8A at 100-127 VAC
3A at 220-240 VAC
Power
usage
For more information
on power consumption,
see Oracle Server X6-2
Power Calculator.
For more information
on power consumption,
see Oracle Server X6-2
Power Calculator.
For more information
on power consumption,
see Oracle Server X6-
2L Power Calculator.
Server node
Maximum: 336W
Typical: 142W
Storage shelf
Maximum: 455W
Typical: 256W