Oracle Database Appliance Specifications
Chapter2 • Overview of Oracle Database Appliance 51
Electrical Specifications for Oracle Database Appliance
Version 1 and Models X3-2, X4-2 and X5-2
Item Oracle Database Appliance
Version 1
Oracle Database Appliance
X3-2/X4-2
Oracle Database Appliance
X5-2
Server node
power supply
output rated
maximum
1270W at 100-120 VAC
1370W at 200-240 VAC
600W at 100-127 VAC
600W at 200-240 VAC
600W at 100-127 VAC
600W at 200-240 VAC
Server node
AC power
12A at 110-127 VAC
7A at 200-240 VAC
13A at 100 VAC (Japan only)
7.2A at 100-127 VAC
3.4A at 200-240 VAC
7.2A at 100-127 VAC
3.4A at 200-240 VAC
Storage shelf
power supply
output rated
maximum
Not supported 580W at 100-127 VAC
580W at 200-240 VAC
580W at 100-127 VAC
580W at 200-240 VAC
Storage shelf
AC Power
Not supported 8A at 100-127 VAC
3A at 220-240 VAC
8A at 100-127 VAC
3A at 220-240 VAC
Power usage Not available Server node
■ X4-2 maximum: 439W
X4-2 typical: 164W
■ X3-2 maximum: 551W
X3-2 typical: 178W
Storage shelf
■ Maximum: 699W
■ Typical: 325W
Server node
■ Maximum: 727W
■ Typical: 508W
Storage shelf
■ Maximum: 699W
■ Typical: 469W
Environmental Specifications
This section describes the environmental specifications for a single, non-racked Oracle
Database Appliance.
Environmental Specifications for Oracle Database Appliance
X6-2 Series
Item Oracle Database
Appliance X6-2S
Oracle Database
Appliance X6-2M
Oracle Database
Appliance X6-2L
Oracle Database
Appliance X6-2-HA
Operating
temperature
5
°
C to 35
°
C (41
°
F to
95
°
F).
5
°
C to 35
°
C (41
°
F to
95
°
F)
5
°
C to 35
°
C (41
°
F to
95
°
F)
5
°
C to 35
°
C (41
°
F to
95
°
F)