Technical Support
Chapter2 • Overview of Oracle Database Appliance 53
Item Oracle Database Appliance
Version 1
Oracle Database Appliance
X3-2/X4-2
Oracle Database Appliance
X5-2
Operating
humidity
10% to 90% relative humidity,
noncondensing
10% to 90% relative humidity,
noncondensing
10% to 90% relative humidity,
noncondensing
Nonoperating
humidity
Up to 93% relative humidity,
noncondensing.
Up to 93% relative humidity,
non-condensing
Up to 93% relative humidity,
non-condensing
Operating
altitude
Up to 3000 m* (9,840 ft).
Maximum ambient temperature
is derated by 1
o
C per 300 m
(984 ft) above 900 m (2,953 ft)
* Except in China markets
where regulations might limit
installations to a maximum
altitude of 2,000 m (6,562 ft).
Up to 3,048 m* (10,000 ft);
maximum ambient temperature
is derated by 1° C per 300 m
above 900 m
* Except in China where
regulations might limit
installations to a maximum
altitude of 2,000 m (6,562 ft).
Up to 3,048 m* (10,000 ft);
maximum ambient temperature
is derated by 1° C per 300 m
above 900 m
* Except in China where
regulations might limit
installations to a maximum
altitude of 2,000 m (6,562 ft).
Nonoperating
altitude
Up to 12,000 m (39,370 ft) Up to 12,000 m (39,370 ft) Up to 12,000 m (39,370 ft)
Cooling Not available Server node
■ X4-2 at maximum usage:
1498 BTU/h
X4-2 at typical usage: 560
BTU/h
■ X3-2 at maximum usage:
1744 BTU/h
X3-2 at typical usage: 607
BTU/h
Storage shelf
■ At maximum usage: 2385
BTU/h
■ At typical usage: 1108
BTU/h
Server node
■ At maximum usage: 2482
BTU/h
■ At typical usage: 1734
BTU/h
Storage shelf
■ At maximum usage: 2385
BTU/h
■ At typical usage: 1600
BTU/h
Acoustic
noise
7.8 B operating, 7.1 B idling
(LwAd: 1 B=10 dB)
7.9 B operating, 5.58 B idling
(LwAd: 1 B=10 dB)
7.0 Bels A-weighted operating,
7.0 Bels A-weighted idling
Technical Support
For technical support, go to:
https://support.oracle.com
When requesting technical support for Oracle Database Appliance, report the following to
Oracle Support Services: