EasyManua.ls Logo

OutBack Power FLEXmax 60 - Wiring Compartment

OutBack Power FLEXmax 60
112 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Installation
900-0009-01-00 Rev C 11
Wiring Compartment
WARNING: Shock Hazard
Make sure all DC circuit breakers are OFF (open) BEFORE making any wiring
connections. Use a DVM to check for voltage on all wires.
The PV (-) and BAT (-) terminals are connected internally. Only one negative wire may be needed to
connect to the (-) wire lugs if the PV - and BAT- conductors are bonded at the negative bus bar.
See Figure 6, Figure 7, and Figure 8 for sample wiring diagrams.
Figure 5 Wiring Compartment
CAUTION: Equipment Damage
Each FLEXmax requires its own PV array. DO NOT PARALLEL FLEXmax PV+ and PV-
TERMINALS ON THE SAME ARRAY!
An optional battery Remote Temperature Sensor (RTS) is recommended for accurate battery charging.
Only one RTS is needed for multiple OutBack inverter/chargers and charge controller units when the system
includes an OutBack HUB and a system display.
When one RTS is used, it must be connected to the component plugged into the Port 1 of the HUB.
Chassis/Equipment
Ground Lug
Use up to 35 mm
2
(2 AWG) wire
Torque to 4 Nm
(35 in-lb)
MATE/HUB
RJ45 port
Battery Remote
Temp Sensor (RTS)
RJ11 port
Auxiliary output
terminals
Wire terminals
Screw holes for mounting the
charge controller
PV+ PV– BAT– BAT+

Table of Contents

Related product manuals