17.4.3  H15 (Compressor Temperature Sensor Error) 
 
0
-20 -10 0 10 20 30 40 50
5
10
15
20
25
30
35
40
45
50
55
60
65
70
75
80
85
90
95
100
105
110
115
120
1
2
3
Resistance (kΩ)
Temperature (°C)
Sensor (Thermistor) Characteristics
1 Outdoor Temp. Sensor
2 Heat Exchanger Sensor
3 Compressor Tank
 Temp. Sensor
 
17.4.4  H16 (Outdoor Unit CT Disconnection Error) 
 
Troubleshooting 
 
Diagnosis Procedures and Cause
Measures to be Taken
There is a gas leak
Lower than the standard value 
Below 0.7A 
Higher than the
standard value
0.7A and above
There is no gas leak
Check the AC current flowing in the white wire on the outdoor unit 
terminal. (Measure the current when the compressor is rotating almost 
at its maximum operating speed.)
Replace the outdoor unit control board.
Replace the compressor.
Replace the capillary tube or expansion 
valve.
Replace the part from which gas is 
leaking.
Check the gas pressure during the rated cooling operation.
Check for presence of gas leak.