218
14.10 Cooling Low Outdoor Ambient Temperature Protection Control
• When outdoor is operating in Cool Mode if outdoor ambient temperature is below -15°C and compressor is
operating for 15 minutes, compressor will stop.
• When outdoor ambient temperature is less than -10°C, the system will restart.
14.11 Heating High Outdoor Ambient Temperature Protection Control
• When outdoor is operating in Heat mode, if outdoor ambient temperature is more than 35°C and compressor is
operating for 15 minutes, compressor will stop.
• When outdoor ambient temperature is less than 27°C, the system will restart.