15.10 Filter Check Control
This control detects the contamination of filter from the accumulated operation time of indoor unit
Model Filter check time (hour)
Wall mounted 360
Except above 1000
Accumulated time will be multiplied by a correction factor
Fan Number Group Correction factor (%)
Below Lo 50
Below Me 75
Except above 100
To inform user to clean the filter, FILTER RESET display on the wired remote control LCD and FILTER LED on
indoor unit remote control receiver / indicator will blink for 10 seconds each time operation ON and operation
OFF.
Indoor
operation
Filter LED/Filter
RESET LCD
ON
OFF
Blink Blink
10s
10s