230
15.10 Filter Check Control
• This control detects the contamination of filter from the accumulated operation time of indoor unit
Model Filter check time (hour)
Wall mounted 360
Except above 1000
• Accumulated time will be multiplied by a correction factor
Fan Number Group Correction factor (%)
Below Lo 50
Below Me 75
Except above 100
• To inform user to clean the filter, FILTER RESET display on the wired remote control LCD and FILTER LED on
indoor unit remote control receiver / indicator will blink for 10 seconds each time operation ON and operation
OFF.
Indoor
operation
Filter LED/Filter
RESET LCD
ON
OFF
Blink Blink
10s
10s