19.18 Compressor Rotation Failure (F32-10)
Malfunction Decision Conditions
A compressor rotation failure is detected by checking the compressor running condition through the position
detection circuitry in the outdoor unit PCB (main).
Malfunction Caused
Compressor terminal disconnect.
Faulty outdoor unit PCB (main).
Faulty compressor.
Abnormality Judgment
Continue 4 times in 20 minutes.