259
19.18 Compressor Rotation Failure (F32-10)
Malfunction Decision Conditions
• A compressor rotation failure is detected by checking the compressor running condition through the position
detection circuitry in the outdoor unit PCB (main).
Malfunction Caused
• Compressor terminal disconnect.
• Faulty outdoor unit PCB (main).
• Faulty compressor.
Abnormality Judgment
• Continue 4 times in 20 minutes.
Troubleshooting