322
Combination 50%
Capacity index(kW) 9.00
TC:Total Capacity (kW)、PI:Power Input (kW)
Outdoor Indoor Air Temperature (°CDB)
Air Temp. 16.0 18.0 20.0 21.0 22.0 24.0
(°CWB) TC PI TC PI TC PI TC PI TC PI TC PI
kW kW kW kW kW kW kW kW kW kW kW kW
-15 10.2 3.11 9.58 2.96 9.00 2.81 8.71 2.73 8.42 2.66 7.84 2.52
-13 10.2 2.97 9.58 2.83 9.00 2.69 8.71 2.62 8.42 2.55 7.84 2.42
-11 10.2 2.85 9.58 2.72 9.00 2.59 8.71 2.52 8.42 2.46 7.84 2.33
-10 10.2 2.79 9.58 2.67 9.00 2.54 8.71 2.48 8.42 2.42 7.84 2.29
-9.1 10.2 2.75 9.58 2.62 9.00 2.50 8.71 2.44 8.42 2.38 7.84 2.26
-7.6 10.2 2.67 9.58 2.55 9.00 2.44 8.71 2.38 8.42 2.32 7.84 2.21
-5.6 10.2 2.57 9.58 2.47 9.00 2.36 8.71 2.30 8.42 2.25 7.84 2.14
-3.7 10.2 2.51 9.58 2.40 9.00 2.29 8.71 2.24 8.42 2.19 7.84 2.09
-0.7 10.2 2.39 9.58 2.30 9.00 2.20 8.71 2.15 8.42 2.11 7.84 2.01
2.2 10.2 2.31 9.58 2.21 9.00 2.12 8.71 2.08 8.42 2.03 7.84 1.95
4.1 10.2 2.25 9.58 2.16 9.00 2.08 8.71 2.03 8.42 1.99 7.84 1.91
6 10.2 2.21 9.58 2.12 9.00 2.03 8.71 1.99 8.42 1.95 7.84 1.87
7.9 10.2 2.15 9.58 2.07 9.00 1.99 8.71 1.96 8.42 1.92 7.84 1.84
9.8 10.2 2.11 9.58 2.03 9.00 1.96 8.71 1.92 8.42 1.88 7.84 1.81
11.8 10.2 2.07 9.58 1.99 9.00 1.92 8.71 1.89 8.42 1.85 7.84 1.78
13.7 10.2 2.03 9.58 1.96 9.00 1.89 8.71 1.85 8.42 1.82 7.84 1.75
Note:PI of indoor units is not included in the table.