38
Gas side mm (inch) 15.88 (5/8) 15.88 (5/8) 15.88 (5/8)
Diameter
Liquid side mm (inch) 9.52 (3/8) 9.52 (3/8) 9.52 (3/8)
Standard Length m (ft) 23 (75.4) 23 (75.4) 23 (75.4)
Length Range (min – max) m (ft) 20 – 90 (65.6 – 295.2) 20 – 90 (65.6 – 295.2) 20 – 90 (65.6 – 295.2)
Piping
Height Different m (ft) 30 (98.4) 30 (98.4) 30 (98.4)
Fin material Aluminium (Pre Coat) Aluminium (Pre Coat) Aluminium (Pre Coat)
Fin Type Corrugated Fin Corrugated Fin Corrugated Fin
Row x Stage x FPI 3 x 51 x 18 3 x 51 x 18 2 x 51 x 18
Outdoor Heat
Exchanger
Size (W x H x L) mm 1295.4 x 798 x 66 1295.4 x 798 x 66 1295.4 x 798 x 44
Power Supply Outdoor Power Supply Outdoor Power Supply Outdoor Power Supply
Length m (ft) - - -
Power cord
Core x Diameter mm
2
- - -
Thermostat Electronic Control Electronic Control Electronic Control
Protection Device Electronic Control Electronic Control Electronic Control
Maximum °C 43 43 43
Cool
Minimum °C -5 -5 -5
Maximum °C 24 24 24
Outdoor
Operation
Range
Heat
Minimum °C -15 -15 -15
1. Cooling capacities are based on indoor temperature of 27°C Dry Bulb (80.6°F Dry Bulb), 19.0°C Wet Bulb (66.2°F Wet Bulb) and outdoor air
temperature of 35°C Dry Bulb (95°F Dry Bulb), 24°C Wet Bulb (75.2°F Wet Bulb).
2. Heating capacities are based on indoor temperature of 20°C Dry Bulb (68.0°F Dry Bulb) and outdoor air temperature of 7°C Dry Bulb (44.6°F
Dry Bulb), 6°C Wet Bulb (42.8°F Wet Bulb).
3. Heating low temperature capacity, input power and COP measured at 230V, indoor temperature 20°C, outdoor 2/1°C.
4. Heating extreme low temperature capacity, input power and COP measured at 230V, indoor temperature 20°C, outdoor -7/-8°C.
5. Specifications are subjected to change without prior notice for future improvement.