Programming Your Application 6-12
650 Series AC Drive
** Power Dependent Parameters
These parameters (marked with “**” in the Application diagrams) are set to a value depending
on the drive's overall “power-build” indicated by the Product Code. We recommend that you do
not change the Product Code.
230V Build Power Dependent Defaults
Frame 1 Frame 2
Parameter Function Block Tag 0.25kW 0.37kW 0.55kW 0.75kW 1.1kW 1.5kW
MOTOR CURRENT MOTOR DATA 64
1.50 A 2.20 A 3.00 A 4.00 A 5.50 A 7.00 A
FIXED BOOST FLUXING 107 5.00 % 5.00 % 5.00 % 5.00 % 5.00 % 5.00 %
ACCEL TIME REFERENCE RAMP 258 10.0 s 10.0 s 10.0 s 10.0 s 10.0 s 10.0 s
DECEL TIME REFERENCE RAMP 259 10.0 s 10.0 s 10.0 s 10.0 s 10.0 s 10.0 s
230V Build Power Dependent Defaults
Frame 3
Parameter Function Block Tag 2.2kW 3.0kW 4.0kW
MOTOR CURRENT MOTOR DATA 64
9.60 A 12.30 A 16.40 A
FIXED BOOST FLUXING 107
3.00 % 3.00 % 3.00 %
ACCEL TIME REFERENCE RAMP 258
10.0 s 10.0 s 10.0 s
DECEL TIME REFERENCE RAMP 259
10.0 s 10.0 s 10.0 s
400V Build Power Dependent Defaults
Frame 2
Parameter Function Block Tag 0.37kW 0.55kW 0.75kW 1.1kW 1.5kW 2.2kW
MOTOR CURRENT MOTOR DATA 64
1.50 A 2.00 A 2.50 A 3.50 A 4.50 A 5.50 A
FIXED BOOST FLUXING 107
5.00 % 5.00 % 5.00 % 5.00 % 5.00 % 5.00 %
ACCEL TIME REFERENCE RAMP 258
10.0 s 10.0 s 10.0 s 10.0 s 10.0 s 10.0 s
DECEL TIME REFERENCE RAMP 259
10.0 s 10.0 s 10.0 s 10.0 s 10.0 s 10.0 s
400V Build Power Dependent Defaults
Frame 3
Parameter Function Block Tag 3.0kW 4.0kW 5.5kW 7.5kW
MOTOR CURRENT MOTOR DATA 64
6.80 A 9.00 A 12.00 A 16.00 A
FIXED BOOST FLUXING 107
3.00 % 3.00 % 3.00 % 3.00 %
ACCEL TIME REFERENCE RAMP 258
10.0 s 10.0 s 10.0 s 10.0 s
DECEL TIME REFERENCE RAMP 259
10.0 s 10.0 s 10.0 s 10.0 s