9-5 Technical Specifications
650 Series AC Drive
Analog Inputs/Outputs
Terminals AIN1, AIN2, AOUT1.
Inputs Output
Range 0-10V and 0-5V (no sign) set via parameter
S
IP13 (AIN1)
0-10V, 0-5V, 0-20mA or 4-20mA (no sign) set via
parameter
S
IP23 (AIN2)
Absolute maximum input current 25mA in current mode
Absolute maximum input voltage 24V dc in voltage mode
0-10V (no sign)
Maximum rated output
current 10mA, with short
circuit protection
Impedance
Voltage input 20kΩ
Current Input <6V @ 20mA
Resolution 10 bits (1 in 1024) 10 bits (1 in 1024)
Dynamic Response Sampled every 10ms Bandwidth 15Hz
Digital Inputs
Terminals DIN1, DIN2, DIN3, DIN4.
Operating Range 0-5V dc = OFF, 15-24V dc = ON
(absolute maximum input voltage ±30V dc)
IEC1131
undefined state
15V
5V
0V
24V
ON
OFF
Input Current 7.5mA @ 24V
Sample Interval 10ms
Digital Outputs
Terminals DOUT2 (DOUT1 is reserved for future models).
Nominal Open Circuit Output Voltage 23V (minimum 19V)
Nominal Output Impedance
33Ω
Rated Output Current 50mA
Cabling Requirements for EMC Compliance
Power Supply Cable Motor Cable Brake Resistor Cable Signal/Control Cable
Cable Type
(for EMC Compliance)
Unscreened Screened/armoured Screened/armoured Screened
Segregation
From all other wiring
(clean)
From all other wiring (noisy)
From all other wiring
(sensitive)
Length Limitations
With Internal AC Supply
EMC Filter
Unlimited *25 metres
25 metres
25 metres
Length Limitations
Without Internal AC
Supply EMC Filter
Unlimited 25 metres 25 metres 25 metres
Screen to Earth
Connection
Both ends Both ends Drive end only
Output Choke
300 metres
maximum
* Maximum motor cable length under any circumstances