EasyManua.ls Logo

Parker 650 Series - Hexadecimal Representation of Trips

Parker 650 Series
70 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Trips and Fault Finding 7-4
650 Series AC Drive
Hexadecimal Representation of Trips
The tables below show the possible parameter values for the AUTO RESTART TRIGGERS and
AUTO RESTART TRIGGERS+ parameters,
S
ST23 and
S
ST24 respectively. Refer to the 650V
Software Product Manual, "Trips Status" (on our website: www.SSDdrives.com) for additional
trip information that is available over the Comms.
Each trip has a unique, four-digit hexadecimal number number as shown in the tables below.
S
ST23 : AUTO RESTART TRIGGERS
ID User
Trip Name
(MMI 6901)
Trip Name
(MMI 6511 & 6521)
Mask
Disable
1 OVERVOLTAGE DCHI 0x0001
2 UNDERVOLTAGE DCLO 0x0002
3 OVERCURRENT OC 0x0004
4 HEATSINK HOT 0x0008
5 EXTERNAL TRIP ET 0x0010
9
6
INVERSE TIME
0x0020
7
CURRENT LOOP
0x0040
9
8
MOTOR STALLED
0x0080
9
9
ANIN FAULT
0x0100
9
12
DISPLAY/KEYPAD
0x0800
9
13 LOST COMMS SCI 0x1000
9
14 CONTACTOR FBK CNTC 0x2000
9
S
ST24 : AUTO RESTART TRIGGERS+
ID User
Trip Name
(MMI 6901)
Trip Name
(MMI 6511 & 6521)
Mask +
Disable
17
MOTOR OVERTEMP
0x0001
9
18 CURRENT LIMIT I HI 0x0002
21 LOW SPEED OVER I LSPD 0x0010
22 10V FAULT T 4 0x0020
9
24 SHRT SHRT 0x0080
25 DC LINK RIPPLE DCRP 0x0100
9
26 DBSC DBSC 0x0200
28 ANOUT FAULT T 5 0x0800
9
29 DIGIO 1 (T9) FAULT T 9 0x1000
9
30 DIGIO 2 (T10) FAULT T 10 0x2000
9
31 UNKNOWN TRIP 0x4000
33 ICAL ICAL 0x8000
Keypads (MMIs):
Trips shown as MMI displays in the tables above, i.e. , can be disabled using the
keypads in the TRIPS menu. Other trips, as indicated, can be disabled over the Comms.
6521
6901
6511
Lefflersgatan 1, SE-754 50 Uppsala, SWEDEN +46 (0)18-65 70 00 +46 (0)18-10 74 78 info@regal.se www.regal.se