Installer Manual Fleck 3150 - NXT - Programming
Ref. MKT-IM-010 / B - 28.05.2018 61 / 122
6.5.4. System type
Select the system in which the valve(s) operate(s).
Options:
•4: single valve;
• 5: multiple valve with lockout;
• 6: multiple valve with consecutive regenerations;
• 7: duplex alternating;
• 9: multiple valve, alternating;
• 14: multiple demand valves.
6.5.5. Valve address in the system
Set the valve position in the system.
Note
Only visible in systems 5, 6, 7, 9 and 14.
Note
The number #1 is the lead valve (master) and contains the programmed parameters used
by the other controllers in the system in order to control the regeneration and service or
standby positions.
Options:
• address #1: valve 1, lead (master);
• address #2: valve 2;
• address #3: valve 3;
• address #4: valve 4.
D Set the system type with and .
Example: 4 Single valve
E Press to validate the selection and advance to the next
parameter.
SYSTEM TYPE :4
SIMPLEX
Example: 5 multiple valves
5#1 SRV* 10:15HR
VOLUME 25000L
F Set the valve position with and .
Example: Valve #1 (master)
→ Default setting: valve 2 address #2.
G Press to validate the selection and advance to the next
parameter.
VALVE ADDRESS
#1
Example: Valve #2
VALVE ADDRESS
#2