Installer Manual Fleck 3150 - NXT - Programming
70 / 122 Ref. MKT-IM-010 / B - 28.05.2018
6.5.20. Flow meter selection
Select the size of the flow meter.
Options:
• 1" paddle;
•1" turbine;
•1½" paddle;
•1½" turbine;
• 2" paddle (std for 3150);
• 3" paddle;
•generic meter.
6.5.20.1 Generic meter
Note
Only visible if "generic" was selected in flow meter selection.
Set the generic meter.
Note
This parameter has two settings. The first one determines the volume which activates the
relay. The second one determines how long the relay has to be activated.
BE Select the flow meter with and .
BF Press to validate the selection and advance to the next
parameter.
FLOW METER
2.0"PADDLE
BG Set the maximum flow rate with , and .
BH Press to validate the selection and advance to the next
parameter.
BI Set the number of litres per pulse with , and .
BJ Press to validate the selection and advance to the next
parameter.
Example: 290 L/min
PEAK FLOW
0290 lpm
Example: 1 litre for 1 pulse
ADD 001 LITERS
EVERY 001 PULSES
Example: 5 litres for 1 pulse
ADD 005 LITERS
EVERY 001 PULSES
Example: 2 litres for 10 pulses
ADD 002 LITERS
EVERY 010 PULSES