Installer Manual Fleck 3150 - NXT - Programming
Ref. MKT-IM-010 / B - 28.05.2018 69 / 122
6.5.19.2 Chemical pump
Activate the relay output during the service based upon the volume of treated water.
Note
Only visible in metered systems.
Note
This parameter has two steps. The first one determines the volume which activates the
relay. The second one determines how long the relay has to be activated once the volume
has passed.
Relay disabled 10 min. after
the start of regeneration
AUX RELAY OUTPUT
END: 00:10:00
Relay enabled during cycle 2
as in chapter 6.5.18.
AUX RELAY OUTPUT
START: 00:10:00
AUX RELAY OUTPUT
END: 01:20:00
AY Activate the relay with and .
→ Default setting: disabled
AZ Press to validate the selection and advance to the next
parameter.
BA Set the relay activating time with , and .
BB Press to validate the selection and advance to the next
parameter.
BC Set the relay deactivating time with , and .
BD Press to validate the selection and advance to the next
parameter.
Disabled
CHEMICAL PUMP:
DISABLED
Relay enabled every 20 litres
CPO AUX RELAY
VOLUME: 0020 L
Relay enabled for 1 min.
CPO AUX RELAY
TIME: 00:01:00