Installer Manual Fleck 3150 - NXT - Troubleshooting
Ref. MKT-IM-010 / B - 28.05.2018 93 / 122
10.3. Examples of error displayed
The unit 2 has been reset;
→ Reprogram the unit.
DETECTED ERROR =
E2 RESET UNIT
there is no message from unit 3;
→ The number indicate the unit to be checked in the system.
ERROR DETECTED
NO MESSAGE 3
→ Check that communication cables are connected.
→ Check the valve address.
there are more units in the system than programmed in the lead
(#1) unit;
ERROR DETECTED
SYSTEM SIZE !
the programmed values do not match, check the values
programmed in each unit;
ERROR DETECTED
ERROR PROGRAM
→ Example: Display format different from one unit to the other.
→ Example: System of 4 units, but only 2 detected or connected.
the programmed position of units incorrect.
→ Lead unit (#1) not programmed.
→ 2 or more units are programmed with the same address.
ERROR DETECTED
ADDRESS OK