Ordering data and technical data
107708_en_09 PHOENIX CONTACT 87 / 104
IEC 61131 runtime system
Number of data blocks depending on data storage
Number of control tasks 32 (16 per processor core)
Cycle Time 1 ms ()
Program memory 8 Mbyte
Data storage 12 Mbyte
Retentive data storage 48 kByte (NVRAM)
Conformance with EMC Directive 2014/30/EU
Immunity test in accordance with EN61000-6-2/IEC61000-6-2
Electrostatic discharge
(ESD) EN61000-4-2/IEC61000-4-2
Criterion B, 6 kV contact discharge, 8 kV air discharge
Electromagnetic fields EN61000-4-3/IEC61000-4-3 Criterion A, Field intensity: 10 V/m
Fast transients (burst) EN61000-4-4/IEC61000-4-4 Criterion B, 2kV
Transient overvoltage (surge)
EN61000-4-5/IEC61000-4-5
Criterion B, DC supply lines: ±0.5 kV/±0.5 kV
(symmetrical/asymmetrical), fieldbus cable shield: ±1 kV
Conducted interference EN61000-4-6/IEC61000-4-6 Criterion A, Test voltage 10 V
Noise emission test in accordance with
EN61000-6-4/IEC61000-6-4
NOTE: radio interference
This is a Class A item of equipment. When using the equipment in residential areas, it may cause radio
interference. In this case, the operator may be required to implement appropriate measures and to pay the
resulting costs.
Approvals
For the current approvals, go to: www.phoenixcontact.net/product/2404267
ATEX (TÜV19ATEX8356X) II 3 G Ex ec IIC T4 Gc
ENIEC60079-0:2018
ENIEC60079-7:2015+A1:2018
IECEx (IECExTUR19.0031X) Ex ec IIC T4 Gc
IEC60079-0:2017, Edition7
IEC60079-7:2017, Edition5.1
UL, USA / Canada (E238705) cULus
UL Ex, USA / Canada (E366272) Class I, Zone 2, AEx nA IIC T4, Ex nA IIC Gc T4
Class I, Div. 2, Groups A, B, C, D
UL60079-0:2013, Edition6
UL60079-15:2017, Edition4
CSAC22.2NO.60079-0:2015, Edition3
CSAC22.2NO.60079-15:16
Corrosive gas test ISAS71.04.2013 G3 Harsh Group A,
DINEN60068-2-60:2016-06 Method4
Industrial Cyber Security (IITS20294290027Rev.00) IndustrialITSecurity, IACSComponent
IEC62443-4-1:2018
IEC62443-4-2:2019
PPP15003B:2021 (IEC62443-4-1: Full ML3 Process Profile)
Configuration: SecurityProfileactive