EasyManua.ls Logo

Pivot ATLAS - 11.4. Configuration >> Alarm Settings

Default Icon
44 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
ATLAS 25 of 44 User’s Manual
11.4. Configuration >> Alarm Settings
Each system alarm is individually configurable as shown in example Figure 11.4-1. The table below outlines
the alarms available on the Configuration >> Alarm Settings page, as well as the trigger level units and
trigger level valid values for each alarm. Furthermore, each alarm can be individually configured as follows:
A delay can be set between 0-1440 minutes. If the alarm condition clears itself within the delay time,
the alarm is not generated.
A priority of “Major”, “Minor, and “Warning” can be selected. “Major alarms are displayed as Red on
the Dashboard” page. Minor” alarms are displayed as Yellow on the Dashboardpage. “Warnings
are displayed as Green on the Dashboardpage. See Section 11.1 for examples. Warning alarms
do not trigger the RED UIM alarm LED to be ON.
Manual clearing can be enabled or disabled. If enabled, the alarm will not automatically clear itself if
the alarm condition no longer persists and manual clearing is required. THIS FEATURE IS
CURRENTLY NOT ACTIVE.
Activation of the ALARM RELAYterminal contacts on the UIM can be enabled by selecting the "K1"
in the RELAY column of the alarm settings for each alarm type.
Deactivation of the. “ALARM RELAY” terminal contacts on the UIM can be enabled by s electing the
"--" in the RELAY column of the alarm settings for each alarm type. With this selected only alarms
with "K1" selected will trigger the contact to change states.
Name
Trigger Level Units
Trigger Level Valid Values
AC Input Power Lost
None
N/A
AC Input Voltage High
V
90-300
Battery Voltage Low
V/cell
0.80-4.00
Battery Voltage High
V/cell
0.80-4.00
Battery Temperature Low
°C or °F
-40 to 70 °C or -40 to 158 °F
Battery Temperature High
°C or °F
-40 to 70 °C or -40 to 158 °F
Min DC Output Current
A
12V
0.0-80.0 (4 iPMs)
0.0-60.0 (3 iPMs)
0.0-40.0 (2 iPMs)
0.0-20.0 (1 iPM)
24V
0.0-40.0 (4 iPMs)
0.0-30.0 (3 iPMs)
0.0-20.0 (2 iPMs)
0.0-10.0 (1 iPM)
iPM Fault
None
N/A
iPM Communication Lost
None
N/A
iPM Incorrect DC Voltage
None
N/A
UIM Fault
None
N/A
Battery Temp Sensor Fault
None
N/A
Remote DC Voltage Sensing Fault
None
N/A