Model Paramount
four 50
Paramount
four 60
Paramount
four 80
Paramount
four 95
Paramount
four 115
Emissions of nitrogen oxides NO
X
mg/kW
h
18 21 23 25 30
(1) Low temperature means for condensing boilers 30°C, for low temperature boilers 37°C and for other heaters 50°C return temperature (at
heater inlet).
(2) High temperature mode means 60°C return temperature at heater inlet and 80°C feed temperature at heater outlet.
See
Contact details on the back cover.
3.2.3
Technical data
Tab.4 Technical data
Model Para‐
mount
four 30
Para‐
mount
four 40
Para‐
mount
four 50
Para‐
mount
four 60
Para‐
mount
four 80
Para‐
mount
four 95
Para‐
mount
four 115
Product ID no. CE-0085BL0514
IP rating IPx4D
Gas category II
2H3+
Appliance category B
23
, B
23P
, B
33
, C
13X
, C
33X
, C
43X
, C
53
, C
53X
, C
63X
, C
83
, C
93X
Software version V 4.2
Nominal heat input
range
Natural gas
E, LL
Heating
mode
kW 5,6 -
30,0
9,0 -
38,0
10,0 -
50,0
14,0 -
58,0
21,0 -
77,0
20,0 -
95,0
25,0 -
115,0
Effective rated output
range
Natural gas
E, LL
80/60°C kW 5,4 -
29,2
8,7 -
37,0
9,7 -
48,7
13,6 -
56,4
20,3 -
74,9
19,4 -
92,5
24,3 -
111,7
50/30°C kW 6,0 -
31,2
9,7 -
39,6
10,8 -
52,1
15,1 -
60,4
22,6 -
80,2
21,4 -
98,6
26,7 -
119,3
Standard operating efficiency 75/60°C 106
pH value condensate – 4 - 5 4 - 5 4-5 4-5 4-5 4 - 5 4 - 5
Volume condensate 40/30°C l/h 0,83 -
3,00
1,19 -
2,84
1,60 -
4,68
1,78 -
4,71
2,53 -
6,46
2,75 -
8,42
3,85 -
9,61
NO
X
standard emission factor mg/k
Wh
17 20 20 20 20 25 30
CO standard emission factor mg/k
Wh
5 10 10 10 10 20 20
Data for design of the chimney to DIN EN 13384 (room air-dependant operation)
Flue gas temperature Part load/full
load
80/60°C °C 53/66 56/75 58/69 59/71 59/73 59/73 60/77
Part load/full
load
50/30°C °C 33/46 35/53 33/50 34/54 35/54 32/51 33/57
Flue gas mass flow
rate
Natural gas
E, LL
80/60°C g/s 2,8 -
14,8
4,4 -
18,7
4,9 -
24,6
6,9 -
28,5
10,3 -
37,9
9,8 -
46,7
12,3 -
56,6
With natural gas 50/30°C g/s 2,5 -
14,1
4,1 -
18,0
4,5 -
23,5
6,4 -
27,4
9,7 -
36,4
9,1 -
44,8
11,3 -
54,4
Flue gas mass flow
rate
Propane 80/60°C g/s 2,6 -
14,1
4,2 -
17,8
5,6 -
23,5
6.6 -
27.2
9,8 -
36,1
14,1 -
44,6
16,4 -
53,9
for LPG 50/30°C g/s 2,4 -
13,4
3,9-
17,1
5,2 -
22,4
6,1 -
26,1
9,2 -
34,6
13,3 -
42,6
15,4 -
51,7
CO2 content natural
gas
Natural gas
E, LL
% Paramount four 30 - Paramount four 60: 8,3 - 8,8
Paramount four 80 - 115: 8,5 - 9,0
CO2 content LPG Propane % 10,3 - 10,8
Draft requirement mbar 0
3 Technical specifications
14 Paramount four 30 – 115 kW 7658013 - 02 - 15092016