EasyManua.ls Logo

Potterton Paramount four - 9.2 Description of the parameters

Potterton Paramount four
144 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
9.2 Description of the parameters
9.2.1 Time and date
Time and date (1–3)
The regulator has a year clock with setting possibilities for time, day/month
and year. Time and date must be correctly set, so that the heating pro
grams can operate to previously carried out programming.
Summer time (5/6)
The start of summer time can be set under prog. no. 5; the end of summer
time is set under prog. no. 6. The time changing is carried out on the Sun
day following the set date.
9.2.2
Operator section
Change Language (20)
This is where you can change the language of the users prompts.
Information (22)
Temporarily: The information display returns to the basic display after 8
minutes.
Permanently: The information display remains permanently displayed af
ter call-up with the information button.
Contrast of display (25)
You can select the contrast of the display here.
Operation lock (26)
If this function is activated the following operating elements are locked:
Operating mode buttons for heating and drinking water mode
Rotary selector (room temperature comfort setpoint)
Presence button (only room unit)
Programming lock (27)
If this lock is activated, parameters can be displayed but not changed.
Temporary unlocking:
Press OK and ESC simultaneously for at least 3 s. The lock will be re-
activated after leaving the setting level.
Permanent unlocking:
First temporary unlocking, then prog.no. 27 to Off.
Units (29)
Here you can choose between SI units (°C, bar) and US-American units
(°F, PSI).
Save basic settings (30)
The parameters of the regulator are written into the room unit/backed up
(only available for room unit).
Caution
The parameters of the room unit are overwritten! With this, the in
dividual programming of the regulator in the room unit can be en
sured.
Activate basic settings (31)
The data of the operating unit or room unit are written into the control.
Caution
The control parameters are overwritten. The factory settings are
stored in the operating unit.
Activation of prog. no. 31 at the
operating unit
.
The regulator is reset to factory setting.
Activation of prog. no. 31 at the
room unit
:
9 Settings
80 Paramount four 30 – 115 kW 7658013 - 02 - 15092016

Table of Contents

Related product manuals