Fig.15 Connection possibilities with KAS (accessory)
C
33 (3)
C
13
RA-0000116
C
33 (1)
C
33 (1)
C
33 (2)
B
23
B
23
C
33 (1)
C
33 (3)
6.3.2 Permissible flue gas pipe lengths
Paramount four 30 / 40 50 / 60 80 95 115
Flue Type Flue
Size
Max
Flue
Leng
th
(1)
Max.
No of
Bend
s
(90°)
Flue
Size
Max
Flue
Leng
th
(1)
Max.
No of
Bend
s
(90°)
Flue
Size
Max
Flue
Leng
th
(1)
Max.
No of
Bend
s
(90°)
Flue
Size
Max
Flue
Leng
th
(1)
Max.
No of
Bend
s
(90°)
Flue
Size
Max
Flue
Leng
th
(1)
Max.
No of
Bend
s
(90°)
C13 (Balanced
Flue)
(2)
80/1
25
10(5) 2 110/
150
5(5) 2 110/
150
5(5) 2 110/
160
5/5 2 110/
160
5/5 2
C33(1) (Concentric
Vertical)
80/1
25
13 0 110/
180
22 0 110/
180
13 0 110/
180
10/3 0 110/
180
10/3 0
C33(1) (Concentric
Vertical)
110/
160
(3
)
20 0 120/
180
(3)
20 0 120/
180
(3)
C33(2) (Concentric
Vertical)
80/1
25
15(3) 2 110/
180
24(3) 2 110/
180
15(3
)
2 110/
180
18/3 2 110/
180
20/3 2
C33(3) (Concentric
Vertical)
80/1
25
7(3) 2 110/
180
13(2) 2 110/
180
9(3) 2 110/
180
110/
180
B23 (Conventional
Flue)
(3)
80 20(3) 3 110 25(3) 3 110 16(3
)
3 110 20/3 2 110 20/3 2
(1) This is the maximum flue length, the allowable horizontal run within total flue length is shown in brackets.
(2) the maximum flue length shown may give an output reduction of 5 % with the maximum flue shown.
(3) not supplied byPotterton Commercial
6 Installation
7658013 - 02 - 15092016 Paramount four 30 – 115 kW 37