With prim contr/system pump (1880, 1930, 1980)
No: The consumer circuit is supplied without primary control unit/system
pump
Yes: The consumer circuit is supplied from the primary controller on/by
the system pump.
9.2.9 Swimming pool
Setpoint solar heating (2055)
When solar energy is used, the swimming pool is heated to the setpoint
set here.
Setpoint source heating (2056)
When using the generator heating, the swimming pool is heated to the set
point set here.
Charging priority solar (2065)
Setting of which priority the swimming pool will be solar heated. The priori
ty for the DHW and charging buffer is set under Prog. no. 3822.
Priority 1: The swimming pool is heated before the buffer is charged.
Priority 2: The swimming pool is heated while the buffer is charged.
Priority 3: The swimming pool is heated after the buffer is charged.
For more information, see
Charging prio storage tank (3822), page 99
Swimming pool temp max (2070)
This parameter sets whether the swimming pool heating by solar charging
has priority or not. If the swimming pool temp reaches the heating limit set
here, the collector pump is switched off. It is again released if the swim
ming pool temp has dropped by 1°C below the maximum heating limit tem
perature.
With solar integration (2080)
Setting, of whether the swimming pool heating can be done by solar ener
gy or not.
9.2.10 Primary control/feed pump
Flow temp setpoint min (2110) and Flow temp setpoint max
(2111)
With these boundaries a range for the flow setpoint can be defined.
Syst pump on heat gen lock (2121)
This parameter can set whether the system pump is also locked or not
when the generator lock is active.
Off: The system pump is not locked.
On: When the generator lock is active the system pump is also locked.
Mixing valve boost (2130)
For the admixture the boiler flow temperature actual value must be higher
than the requested setpoint of the mixer flow temperature, since this can
not be corrected otherwise. The controller forms the boiler temperature
setpoint from the boost set here and the current flow temperature setpoint.
Actuator running time (2134)
Setting the actuator running time of the mixing valve used.
Primary contr/system pump (2150)
Before buffer: The primary controller/feed pump is arranged with existing
buffer storage tank hydraulically upstream of the buffer storage tank.
After buffer: The primary controller/feed pump is arranged with existing
buffer storage tank hydraulically downstream of the buffer storage tank.
9 Settings
7658013 - 02 - 15092016 Paramount four 30 – 115 kW 93