Configuring Modbus ION 8000 Series User Guide
Page 106 Chapter 7 - Third Party Protocols
Configuring Modbus
Using the Front Panel
You cannot configure Modbus through the meter’s front panel. You can only
assign the Modbus protocol to communication ports. See the Communications
chapter for details.
Using ION Setup
The Modbus Setup Assistant helps you configure Modbus Master and Slave
functionality for your meter.
1. Open ION Setup and connect to your meter, using Basic Mode.
2. In the Setup Assistant, navigate to Communications > 3rd Party Protocols
3. Click on the Modbus Slave tab to edit the Modbus Slave modules.
4. Select the map name (in this example, the default map) and click Edit.