ION 8000 Series User Guide Sliding Window Demand Module Settings
Chapter 9 - Demand Page 117
3. Configure Rolling Block demand by selecting a register and clicking Edit.
You can configure both the Sliding Window Demand and Thermal Demand
modules using Advanced Mode.
1. Connect to your meter, using Advanced Mode.
2. Click on the module you wish to configure.
Using Designer
Open your meter in Designer and navigate to the Demand Setup framework.
There are two sections: Sliding Window Demand setup and Thermal Demand
setup. Right-click on a module to edit.
NOTE
For Time-of-Use Demand setup, go to Advanced Setup > Revenue Framework folder (in Designer).
Sliding Window Demand Module Settings
Sliding Window Demand is often referred to as Rolling Block Demand. To
compute sliding window demand values, the Sliding Window Demand module
uses the sliding window averaging (or rolling interval) technique which divides
the demand interval into sub-intervals.