Restoring the Factory Configuration ION 8000 Series User Guide
Page 42 Chapter 3 - Templates and Firmware
10. Click the Power Meter shortcut in the Basic Configuration area to select it. Once
selected, click Reset in the Designer toolbar, or select Reset from the Edit menu.
This reverts the Power Meter to the settings it had before you deleted any
modules (retaining the basic setup you previously had).
11. Choose Send & Save from the File menu. The factory configuration is now
restored and any custom functionality you created is removed.
NOTE
The time required to complete steps 3, 5, and 11 may vary depending on your connection and the meter
configuration.
Using ION Setup
1. Download your device’s latest template from http://www.pwrm.com/
support/downloads/. Save the .DCF file in the .../ION Setup/TEMPLATE
folder for easy access.
2. Connect to your meter in ION Setup, using Basic Mode.
3. Navigate to Setup Assistant > Template.
4. Click the Send to Meter tab and click the Send button.
5. Select the .DCF file from the TEMPLATE folder and click OK.