Configuring Data Logging ION 8000 Series User Guide
Page 144 Chapter 12 - Logging
Historic Data Logging
Three data recorders are used to record “standard” power system quantities, such
as phase current, phase voltage and power factor. These recorders are labeled Hist
Mean Log, Hist High Log, and Hist Low Log. They are located through this folder
path on the meter’s program: Advanced Configuration > Historic Data Logging.
By default, they log the following ION output register values:
Loss Log
One Loss Log recorder is configured to record loss values. It is located in the
following folder path on the meter’s program:
Advanced Configuration > Revenue framework > Energy framework. By default,
it logs the following ION parameters:
Hist Mean Log Hist High Log Hist Low Log
Vll ab mean I avg mean Vll ab high I avg high Vll ab low I avg low
Vll bc mean I 4 mean Vll bc high I 4 high Vll bc low I 4 low
Vll ca mean kW tot mean Vll ca high kW tot high Vll ca low kW tot low
Vll avg mean kVAR tot mean Vll avg high kVAR tot high Vll avg low kVAR tot low
V unbal mean kVA tot mean V unbal high kVA tot high V unbal low kVA tot low
Ia mean PF lag mean Ia high PF lag high Ia low PF lag low
Ib mean PF lead mean Ib high PF lead high Ib low PF lead low
Ic mean Freq mean Ic high Freq high Ic low Freq low
Parameter Description
MU Ia^2h int Phase A interval current squared hours
MU Ib^2h int Phase B interval current squared hours
MU Ic^2h int Phase C interval current squared hours
MU Vll ab^2h int Phase A interval voltage Line-to-Line squared hours
MU Vll bc^2h int Phase B interval voltage Line-to-Line squared hours
MU Vll ca^2h int Phase C interval voltage Line-to-Line squared hours