Introduction ION 8000 Series User Guide
Page 158 Chapter 14 - Power Quality
Introduction
Power quality configuration is provided by a number of modules, depending on
your meter type: the Sag/Swell module, and the Transient module, some of which
include the Mains Signalling Evaluation modules.
See the ION Reference for more information on these modules.
Configuring Power Quality
Use ION software to change your meter’s power quality settings.
Using the Front Panel
You cannot configure Power Quality from the front panel.
Using ION Setup
The Power Quality Setup Assistant helps you configure the various power quality
modules.
1. Open ION Setup and connect to your meter, using Basic Mode.
2. In the Setup Assistant, navigate to the Power Quality folder.
3. Click on the Sag/Swell tab to set sag and swell limits, configure sag/swell
waveform recorder settings and most importantly, record your system’s nominal
voltage.
4. Click on the Waveforms tab to configure the waveform recording features of the
meter, including the waveform depth, the number and samples per cycle.
5. Click on the Transient tab to configure various settings such as voltage deviation
threshold and transient waveform recorder depth and frequency.