ION 8000 Series User Guide Test Settings
Chapter 23 - Verifying Accuracy Page 221
2. Select the LED Pulsing screen.
3. Edit the kWh and kVARh values as desired.
Changing the LED pulse rate in Designer
1. Open the meter using Designer software and double-click the Pulse Frequency
folder in Energy Pulsing Setup.
2. Right-click the Calibration Pulser module you want to modify.
3. Double-click the register you want, make your change and click OK.
4. Click the Save icon (or choose Send & Save from the File menu).
The value entered defines how much energy the module accumulates before a
pulse is sent to the hardware channel. The front panel WATT and VAR LEDs are
factory set to the same pulse rate. The default Kt value is shown on the front panel
label of the ION 8000 series meter and depends on the Form Factor that the meter
services.
The pulse rates are summarized below:
Form Factor Default pulse rate for WATT LED Default pulse rate for VAR LED (Kt)
9S, 39S, 36S,
76S meters
1.8 Watts per pulse 1.8 VARs per pulse
35S meters 1.2 Watts per pulse 1.2 VARs per pulse