UPS User’s Guide S Rev B www.powerware.com
Chapter 2 Installation Setup
This chap ter explains h ow to setup and install the Powerware 9170
+
cabinets:
Setup, including clearances and location requirements
Caster cart installation
Stabilizer bracket installation (for 12-slot cabinets with non-isolated
output)
Rack-mount installation (for three- and six-slot cabinets)
Floor anchor kit installation
Moving the cabinets
Equipment Clearances
All cabinet sizes require the following clearances to allow for servicing
and adequate ventilation:
Fromthesidepanels: 6I (15.2 cm)
Top and back: 12I (30.5 cm)
Front: 36I (91.5 cm)
If flexible conduit connects the UPS to the service input and load
distribution panels, you may be able to gain access for servicing by
moving the UPS. If this is the case, you must still leave 12I (30.5 cm)
clearance at the back and 6I (15.2 cm) at the sides of the UPS for
ventilation.
NOTE Do not block the ventilation holes on each side and the back of t he
unit.
Nine- and 12-slot external battery cabinets may be installed with bases
tight against the UPS cabinet base and against each other. Six-slot
cabinets require 6I of separation.