13.6 RUNNING IN
For the first 50 hours of operation of the machine do not employ more than 70% of the maximum
power indicated in the technical specifications. In this way, a proper engine running in is
guaranteed.
13.7 USE OF MACHINE
Earth Leakage Circuit Breaker.
The product is equipped with an Earth Leakage Circuit Breaker (ELCB) (31) which guarantees
user protection against electric shocks due to unwanted contact with live parts of the circuit or
insulation fault.
Warning!
In order to guarantee ELCB proper operation, the lighting tower must be connected to the earth.
Earthing must conform to IEC 364 standard.
Verify periodically the operation of the earth leakage circuit breaker (31), by pressing the “TEST”
button placed on the front panel.
The hour meter exclusively indicates the hours of working of the engine because it only works with
the engine in motion. It could be a reference for the periodic ordinary and extraordinary
maintenance of the machine.
13.8 GENERATOR ALARMS
The generating set is equipped by a protection (DAS) that turn off the machine after 20 seconds
from the survey of a failure, signalled visually by the signal lamps placed on the command panel.
When the trouble is removed, a new starting will clear the memory of the DAS.
Low oil pressure.
When the engine oil pressure is too low, the light comes on (24). Check the engine oil level.
High water temperature.
When the engine water temperature is too high, the light comes on (25). Check the engine water
level.
No battery charge.
When the alternator don’t not charge the battery or the battery does not hold loads, the light
comes on (23). Check the alternator and the battery.
Low fuel level.
When fuel level probe, the light comes on (27). Periodically verify the fuel level by the monitor (38).
Fill up the tank with the fuel level is low.