EasyManuals Logo

Procopi ESS PRO User Manual

Procopi ESS PRO
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #52 background imageLoading...
Page #52 background image
52/84
2015/02 - Indice de révision : B - Code : 29650
MANUAL DISMANTLING AND DESCALING OF THE CELL:
1. 

case acid was just injected.
2. Isolate the by-pass loop on which the cell is
mounted by completely closing the shut-off
valves at the loop inlet and outlet.
3. Disconnect the quick connectors of the cell
power cables.
4. Unscrew the white barrel unions on either end of
the cell, and remove the cell.
5. Screw the white blanking cap onto one of the

correctly positioned.
6. Turn the cell the other way round and stand it
vertically on the white cap.
7. Pour white distilled vinegar or 10% Hydrochloric
acid into the cell.
8. 
frothing),
9. If scale is still present, empty the cell and repeat
the procedure with vinegar or acid.
10. Rinse the cell with water.
11. Make sure that the o-rings are in position
at either end of the cell and remount it. Put the
installation back into operational status (cell

WINTERIZING
A) PASSIVE WINTERIZING:

during the winder, proceed as follows to avoid any
damage that could be cause by freezing or clogging
with algae:
Close the two shut-off valves on the by-pass loop
on which the cell and pH-Clear pump are mounted.
PH-CLEAR PUMP:
Rinse the pump tubing as follows to remove any
traces of acid:
Pull the suction tube and strainer carefully
out of the acid buffer tank and immerse it into a
bucket of water.
run the pump either in pH Reducing - Manual


        
emptied, stop the pump.
Disconnect the acid suction tube from the blue
connector on the pump.
Remove the transparent splash guard.
Carefully disconnect the acid injection tube from
the injection nipple and allow water from the
pumping circuit to empty into a bucket placed
below.
CELL:
Descale and clean the cell (ref VIII.5), either
using the pH-Clear pump before it is winterized,
or manually after dismantling the cell (ref. X.5) ;
Open the bottom union to drain water from the
cell, then screw the union shut ;

remove it.
PROBES
Cut the power supply to the electrical/ control
panel;
Disconnect the probes from the electrical/ control
panel;
Close the shut-off valve on the by-pass loop on
which the probes are mounted;
remove the probes and place them in their phials
of buffer solution and store them in an area
protected against freezing.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Procopi ESS PRO and is the answer not in the manual?

Procopi ESS PRO Specifications

General IconGeneral
BrandProcopi
ModelESS PRO
CategorySwimming Pool Cleaners
LanguageEnglish

Related product manuals