Relay Parameters
All relay related parameters are prefixed with a 2**.
The second digit of the three-figure parameter number denotes the relay
number as follows:
21* parameters for Relay 1
22* parameters for Relay 2
The third digit selects specific parameters for the setting up of the relays,
which can be selected individually and results in the following parameter
numbers for each relay.
Relay 1 210 to 218
Relay 2 220 to 228
Relay Type
P210, P220 - Relay Type
This parameter defines what type each relay should be, see the table below or
available options.
Relay not in use or programmed.
Relay is programmed as an alarm relay,
which will de-energise ON, and energise
OFF. This will ensure an alarm is raised if
the power fails to the unit.
Relay is programmed as a control relay,
which will energise ON, and de-energise
OFF.