EasyManua.ls Logo

Pulsar blackbox 130 - Relay Parameters; Relay Type; Relay Function

Pulsar blackbox 130
96 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Page 53
Relay Parameters
All relay related parameters are prefixed with a 2**.
The second digit of the three-figure parameter number denotes the relay
number as follows:
21* parameters for Relay 1
22* parameters for Relay 2
The third digit selects specific parameters for the setting up of the relays,
which can be selected individually and results in the following parameter
numbers for each relay.
Relay 1 210 to 218
Relay 2 220 to 228
Relay Type
P210, P220 - Relay Type
This parameter defines what type each relay should be, see the table below or
available options.
Option
Description
0= Not In Use (Default)
Relay not in use or programmed.
1= Alarm
Relay is programmed as an alarm relay,
which will de-energise ON, and energise
OFF. This will ensure an alarm is raised if
the power fails to the unit.
2= Control
Relay is programmed as a control relay,
which will energise ON, and de-energise
OFF.

Table of Contents