Test Mode
Test mode is used to simulate the application and confirm that all parameters
and relay setpoints have been entered as expected. During simulation, there is
a choice of whether the relays will physically change state (hard simulation)
or not (soft simulation), the LED’s will always change state to indicate that
the relay setpoints have been activated, and the output will change in
accordance to the chosen mode of operation. If you wish to test the logic of
the system that the relays are connected to then select hard simulation, but
if you don’t want to change the relay state, then select a soft simulation.
There are two simulation modes, automatic and manual. Automatic
simulation will move the level up and down between empty level and
maximum span, whereas manual simulation will allow you to move the level
up and down using the arrow keys.
To enter simulation, first go to program mode. Then, using the menu system,
select menu item Testthen sub-menu item Simulation’. Simply change the
value of the parameter P980 to one of the following:
1= Manual soft simulation
2= Automatic soft simulation
3= Manual hard simulation
4= Automatic hard simulation
To return to program mode, press CANCEL and test mode will end.
When in manual simulation, by default test mode will move the level by
0.25m steps. Altering the increment (P981) will change this value.
In automatic mode, the rate at which the level moves up and down is set by
the increment (P981) in feet and the rate (P982) in minutes, which can be
changed to make the level move up and down faster. E.g. if increment (P981)
is set for 0.25ft and rate (P982) is set to 1 min then the level will increase or
decrease at a rate of 0.25ft/min. To make the simulated level move slower,
decrease the value in increment (P981) or increase the value in rate (P982).
To make the simulated level move faster, increase the value in increment
(P981) or decrease the value in rate (P982).