Page 169
Stability Parameters
Damping
Damping is used to damp the display, to enable it to keep up with the
process but ignore minor surface fluctuations.
P870 Fill Damping
This parameter determines the maximum rate at which the unit will
respond to an increase in level. It should be set slightly higher than the
maximum vessel fill rate. Default = 32.8084 feet/min
P871 Empty Damping
This parameter determines the maximum rate at which the unit will
respond to a decrease in level. It should be set slightly higher than the
maximum vessel empty rate. Default = 32.8084 feet/min
Indicator
P872 Fill Indicator
This parameter determines the rate at which the LCD fill indicator activates.
Default = 32.8084 feet/min
P873 Empty Indicator
This parameter determines the rate at which the LCD empty indicator
activates. Default = 32.8084 feet/min
Rate
P874 Rate Update
This parameter determines the way in which the rate is calculated. If set to
continuous (P874=0), then the rate is calculated and displayed
continuously, i.e. any change seen from shot to shot is calculated and
displayed, but if set to use values P874=1(Default) then the values set in
P875 and P876 are used to calculate and display the rate.
P875 Rate Time
This parameter is the period (in seconds) over which the material level rate
of change is averaged before the Rate Value (P877) is updated. If the Rate
Distance (P876) is exceeded before the Rate Time (P875) has expired, then
the Rate Value (P877) will be updated immediately. Default = 60sec.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Pulsar Ultra 3 (UL) and is the answer not in the manual?

Pulsar Ultra 3 (UL) Specifications

General IconGeneral
BrandPulsar
ModelUltra 3 (UL)
CategoryMeasuring Instruments
LanguageEnglish

Related product manuals