Page 134 
General Control 
 
When Ultra Wizard = 1 Level/Volume   
P210, 220, 230 =2 (General Control) 
When  a  relay  is  being  used  for  a  general  control  function,  the  second 
parameter determines  whether  the  control  is  currently  switched  “ON”  or 
“OFF”. 
P211, P221, P231 - Relay Function, 
This  parameter  defines  whether  the  general  control  relay  function  is 
currently “ON” or “OFF”. 
Relay is always de-energised. 
Control  is  based  on  the  level  in  the  vessel.  All 
general controls are used to assist each other (run at 
the same time) and each general control has its own 
“ON” and “OFF” setpoints.  
 
The third parameter has no function when general control is chosen and 
will not be displayed.  
The fourth parameter and fifth parameter are set to determine the switch 
points for the general control relay. See the general control function, table 
(P211, 221, 231) for further information. 
Important Information 
The general control relays are started and stopped at the “ON” and “OFF” 
setpoints. To control down (reduce level) then set “ON” higher than” OFF”. 
To control up (increase level) then set “ON” lower than “OFF”.  
 
 
P213, P223, P233 - Relay Setpoint 1 
This parameter determines the “ON” point for the general control relay  
Relay Setpoints are entered in values of Measurement Units (P104).