Important Information
Setpoints are entered in values according to the function selected.
Level - entered in Measurement Units (P104) or % of span as referenced to
Empty Level.
Rate of Change - entered in Display Units per minute or % of span per minute.
For an alarm on an increasing level enter setpoints as a positive value, for an
alarm on a decreasing level enter setpoints as a negative value.
Temperature - entered in ºC.
See the appropriate alarm function, table (P211, 221, 231) for further
information.
When P211, 221, 231 = 4 (Loss of Echo) or 5 (Loss of Clock)
This parameter has no function and will not be displayed
* To set figures in % press the hot key to show and enter % figure
relative to empty level.